Power steps
Each running inverter carries one step (500 W by default, adjustable). A 750 W load needs two inverters, not four.
How it works · 1 of 4
When the home draws power, TedEnergy does not call on every inverter in equal shares: it runs the fullest batteries, just as much as needed, and leaves the others asleep. Watch the same evening next to a standard HEMS.
Press “Compare” to see the standard HEMS alongside. Space bar: pause.
The animation
Each running inverter carries one step (500 W by default, adjustable). A 750 W load needs two inverters, not four.
The inverter that starts first receives a small fixed setpoint (50 W by default) while those already running cover the surge. It then takes its share in stages: no spike, no grid import in the meantime.
An inverter is not stopped the moment demand drops a little: TedEnergy waits, to avoid pointless stops and restarts, and keeps one inverter active as long as the discharge continues.
A battery just above its minimum level does not restart for a few watts: it waits until it is above a restart margin.
Simplified animation with default values: the model follows TedEnergy's principles, it is not a recording. The standard HEMS is basic control used for comparison, not a particular product. The effect on hardware lifetime has not been measured by a laboratory.
Because every start and stop stresses the inverter and its battery, and a lightly loaded inverter is less efficient. Concentrating power on the fullest batteries and letting the others sleep limits that stress.
No: while an inverter wakes up, the ones already running absorb the power surge. The meter stays as close to zero as possible.