Documentation · 3.8.1
How TedEnergy regulates
Operating modes, discharge, surplus charging, scheduled charging, sharing between inverters and protections, with the settings that control them.
Documentation up to date with TedEnergy 3.8.1.
The principle
TedEnergy reads the meter power at every new measurement and works out what the controlled inverters must do: discharge to cover consumption, charge with surplus solar, or stay idle. There is no fixed rhythm: as soon as a measurement changes, the setpoint is recalculated. TedEnergy accounts for what it has already requested and the inverters have not yet applied.
Everything is set from the interface, with no restart; changes apply on the next cycle. Defaults suit most installations: when in doubt, change nothing, and adjust one setting at a time, watching the result for a day.
The four modes
Only one mode is in charge at any moment. Settings › Operating modes lets you enable each one or not; when in doubt, leave them enabled: a mode with nothing to do does no harm.
- Scheduled charge: a slot of your calendar, or a chosen tariff period, is under way. Batteries charge even without sun, from the grid. This mode has priority over the others.
- Assisted: at least one monitored inverter (one of a manufacturer's HEMS) is declared. Your controlled inverters complete this HEMS.
- Autonomous: no monitored inverter. TedEnergy manages all batteries by itself: it keeps the meter around a target by discharging, and charges with surplus solar. This is the normal mode.
- Standby: nothing to do (no active mode, invalid license, meter measurement unavailable, no usable inverter). No setpoint is sent.
Autonomous mode
When discharging, battery power is adjusted so the meter shows the chosen target (Settings › Autonomous mode). A slightly positive target deliberately leaves a little grid import, which makes batteries last longer and avoids calling them for tiny powers; a negative target accepts a little export.
- Different target by period of the year: you define ranges (for example winter and summer), each with its own target.
- Maximum increase and decrease of discharge at each recalculation, and the share of the gap corrected each time: fine settings for a more reactive or gentler regulation.
- The inverter stays idle while the consumption to cover is too small to justify a start, then wakes up gradually as it increases.
Surplus solar charging
When the panels produce more than the house consumes (negative meter), batteries charge with this surplus, in Autonomous and Assisted modes. Two methods, to choose in Settings › Surplus solar charging:
- Standard charging: it starts when export exceeds a threshold for a confirmation delay, then keeps the meter close to that threshold and stops when export drops. Simple and predictable.
- Optimised charging (experimental, at least two controlled inverters): two inverters stay awake at low power, one charging (the emptiest), the other discharging (the fullest), and absorb every variation. Surplus goes to the first, consumption to the second, with no threshold or delay and no stop and start at every cloud. The dashboard then shows a small discharge during charging, which is normal.
Two settings common to both methods guard against useless charging: charging only starts if the panels are producing enough (no charging at night on a brief export) and the triggering export cannot be set too low. The maximum charge variation at each recalculation sets the ramp-up speed.
A restart margin stops an almost full battery from immediately charging again.
Assisted mode
With a manufacturer's HEMS that keeps its own devices, your controlled inverters complete it: they discharge in proportion to what the monitored inverters deliver. Settings › Assisted mode sets the share of the monitored power taken over by your devices, the maximum variation at each change and how long a setpoint is held, to avoid oscillations with the manufacturer's HEMS.
Scheduled charging
During a slot, batteries charge from the grid even without sun, typically in off-peak hours. The source of slots is single, to choose: your manual weekly calendar (ticked half-hours) or the tariff periods of your subscription that you tick (see Tariffs, balance and reports).
- Maximum grid power during charging: it never exceeds the subscription. When the house consumes, charging is shed so as not to exceed the limit.
- Finish charging together: inverters share the work so as to finish at the same time.
- In three-phase, a maximum power per phase applies.
- The Store's Scheduled-charge preparation feature balances the batteries before the slot (see The Store).
Sharing between inverters
When you have several controlled inverters, TedEnergy decides how many work and which ones. Settings › Sharing between inverters sets these choices:
- One more inverter every…: the power per active inverter. The lower it is, the more inverters work at low power; the higher, the fewer inverters work.
- Discharge priority: in each inverter's sheet, low, medium or high. Inverters whose panels are producing go first (solar priority), then high, medium and low priorities; at equal priority, the fullest battery. When charging, the emptiest goes first. A low-priority inverter can be “integrated” like the others when its battery is clearly fuller.
- Minimum working time: a started inverter stays active a minimum time, to avoid endless stops and starts.
- Battery gap to change inverter: avoids replacing one inverter with another for a small level difference.
- Wake-up setpoint and gradual transfer: an inverter that starts first receives a small setpoint while it wakes up (this can take from a few seconds to several tens of seconds depending on the brand); inverters already active take the rest, then the load rebalances in steps.
- In Autonomous discharge, an inverter can stay awake at low power so that resuming is immediate.
The start-up times measured for each inverter are visible in Diagnostic › Start-up times. They help spot an abnormally slow device.
Battery and power protections
- Minimum and maximum battery levels, general or specific to each inverter: the most cautious limit always applies.
- Maximum charge and discharge powers, capped by your subscription (subscribed power is entered in Settings › Subscription and tariffs).
- Power really accepted: TedEnergy learns the power each battery really accepts (an almost full battery or one limited by cold) and does not insist beyond it.
- Electrical panel protection: battery discharge adds to what the grid sends into the panel. If the total exceeds the limit (your subscription with a margin), discharge is cut, a red bar appears at the top of every page and you are notified. It resumes by itself when things are back to normal, or with the Restart regulation button. This protection only acts on controlled inverters. If your panel handles more than your subscription and an electrician has checked it, the Store's My panel's capacity feature raises the limit.
Error 01 and error 02: setpoint not applied
Sometimes an inverter accepts a setpoint without producing it. TedEnergy detects this, sets the inverter aside (red line, ⚠ icon) then tests it regularly with a small power in the regulation's direction. If it produces it, it is unblocked and stays a priority for a while.
- Error 01: the inverter does not apply its setpoint, in charge or in discharge.
- Error 02: the test is impossible for now (battery full during a charge, at minimum during a discharge, solar passing through the inverter…). The test starts as soon as the cause disappears.
- The ⚠ icon lets you force a new try without waiting; the ⋮ menu also offers a forced unblock.
- The detection delay, tolerance and test frequency are set in Settings › Monitoring and safety; an illustration shows each setting's effect. An inhibition checkbox in the device sheet disables detection for a device whose behaviour is normal.
Other protections
- Setpoint changed by another system (manufacturer app, third-party integration, Home Assistant automation): TedEnergy pauses the inverter for a few minutes, shows it clearly (“other system, restored at…”) then takes control back. The pause length is adjustable; 0 disables detection.
- Setpoint not applied (an idle inverter that keeps discharging, for example): TedEnergy rewrites the setpoint, then, if the problem persists, pauses the inverter and alerts you.
- Measurements not received: an inverter whose measurements stop arriving is set aside until they return, with a clear message. At TedEnergy's start, waiting for the first measurements is shown without a false alarm.
- Calibration: during a battery calibration, the inverter is not controlled; the Store's Scheduled calibration feature prepares full batteries.
- Failed commands: an inverter that stops answering is set aside then retried automatically.
- License: if a license limit is exceeded, the extra inverters are disabled, with a warning.
Three-phase grid
In three-phase, Settings › Electrical grid chooses the grid type and the regulation: on the sum of phases (the case with a Linky meter, which adds them) or phase by phase. Each inverter is attached to its phase. A three-phase or high-power station requires an installation declared as three-phase with regulation on the sum.
Fine settings and good practice
- Settings › Rhythm and stability sets the regulation loop: measurement smoothing, anti-oscillation. Defaults are fine.
- Download your configuration (Settings › Backup and versions) before any major change.
- Test a new inverter before enabling it and check its maximum powers.
- Keep a reasonable minimum battery level to preserve its lifespan.
- If in doubt about the electrical installation, have it validated by a professional.
- An AI can help you spot what works badly: Settings › Tune with an AI.
Frequently asked questions
Why is only one inverter working when I have six?
TedEnergy makes the useful number of inverters work: one more per power band. For a small consumption, one is enough. Setting: One more inverter every….
Why aren't my batteries discharging while I consume?
Several possible causes: minimum level reached (or restart margin), inverter disabled or faulty, wake-up setpoint in progress, positive meter target, or Standby mode. The status banner and the inverter's sheet give the reason in plain words.
Why isn't it charging while I export?
Surplus charging starts after a confirmation delay, only if the panels produce enough, and not if the battery is almost full. See also optimised charging, which has no threshold or delay.
An inverter is in error 01, what should I do?
Usually nothing: TedEnergy tests it regularly and unblocks it by itself. You can force a try with the ⚠ icon. If it keeps happening, see Troubleshooting and glossary.